LX-485

Illuminance control

Illuminance control


Product description

LX-485 is a high-precision lux meter probe with a wide measurement range, which has an RS-485 connection and Modbus protocol for direct and remote illuminance transmission without any accurate loss in the measurement by the wire length.

Direct and continuous transmission of the luxometric level of an installation's outdoor or indoor part to a lighting control system that allows the regulation of light levels to use the electrical energy needed, depending on the lighting levels.

LX-485 lux meter is designed to measure illuminance with a similar curve as the human eye due to its exclusive filter and diffuser. The measurement precision is automatically adjusted according to the scale, which allows a wide measurement range with high precision.

RS-485 connection allows remote data communication placing the probe in the right place without loss of precision in the measurement due to the distance of the connection wire with the control unit.

Modbus protocol is used to transmit the luxometric value without converting the analogue signal and processing the value for its translation into an illuminance measurement.

Its compact design and fastening using a screw and magnet make the set-up easy and quick in the most suitable location.

Features

  • Illuminance capture and processing quickly and automatically.
  • Data transmission without loss of precision in the measurement, derived from the connection distance of the sensor with the control unit.
  • Modbus communications protocol.
  • Sending the value directly in luxes.
  • Luxes an integer value or with a decimal.
  • Identification of the scale used in each measurement.
  • Assignment of the peripheral number for a RS485 network creation .
  • Simple to install and place in the right place.
  • Easy dome to clean and maintain.

Technical specifications

  • Planar silicon PN photodiode in a hermetically sealed shell specially designed for high precision linear applications.
  • Measuring range from 0 to 50.000 Lux.
  • Automatic scaling with a resolution of 0,1 to 13,5 Lux.
  • Filter with a response similar to that of the human eye.
  • Diffuser to adapt the angular response of the sensor to the cos(α) curve between -80º and 80º.
  • Includes a 12-bit A/D converter to convert the measurement into luxes.
  • Output via RS485 channel.
  • RS485 and power cable of 2.5 meters included in the LX-485.
  • Maximum communication distance with RS485 cable is 1200 meters.
  • Supply voltage from 5 to 15 V d.c.
  • Maximum supply current 20 mA.
  • Transparent PC-V0 polycarbonate dome.
  • Protection degree IP65.
  • Dimensions Ø88 x 75 mm and weight of 170 gr.
  • Securing the probe using a magnet and M6 screw (max. depth 9 mm).
  • Includes initial calibration certification.