TELEASTRO MB TCP

Lighting telemanagement with open protocol

Lighting telemanagement with open protocol


Product description

TELEASTRO MB TCP is the control unit for the public lighting electrical panel that includes a high-performance astronomical clock, reading of electrical parameters for monitoring energy efficiency, access control and panel status, the measurement of the electrical insulation of the installation and the operation control of the electrical protections.

It incorporates the open MODBUS TCP protocol, which allows its integration in most Smart City platforms, in building management systems (BMS) or in supervision and control programs (SCADA). It is specially designed for communication over an IP network using a GPRS modem, Ethernet network and Wi-Fi link

With the MODBUS TCP protocol, we can read the alarms recorded by the TELEASTRO MB TCP, the automatic and periodic records of the electrical measurements, as well as program the manoeuvres and configure the alarms.

The alarms associated with the electrical parameters, the digital inputs and their operating mode ease the supervision of the installation in real-time.

There is the possibility of associating additional alarms for minutes elapsed to the open door and manual panel digital alarms so that we can control the inappropriate use of the lighting panel.

Allows the creation of astronomical calendars and personalized schedules independently for each of the four manoeuvre outputs, allowing the control of the lighting, the saving system, the ornamental lighting or other elements on which we want to act.

Features

  • Astronomical calculation day by day using an exclusive high-precision algorithm.
  • Precision of geographic coordinates in degrees and minutes.
  • Four independent output circuits with astronomical and time programming.
  • Up to 8 manoeuvres per day with astronomical and hourly programming for each departure.
  • Astronomical adjustable in ±240 minutes from the calculation of sunrise and sunset.
  • Multiple programming options by type of days/range: annual, by days of the week, by date range or times of the year and by holidays for one or all years.
  • Memory for 90 types of days/range and 500 manoeuvres (max. 8 manoeuvres per type of day/range).
  • Automatic calculation of Holy Week and related days (Carnival, Corpus).
  • Control and command of manoeuvres, regardless of any communication problem with the control system.
  • Basic configuration via keyboard and advanced via Modbus TCP.
  • Remote control of the manoeuvre outputs, by keyboard, by SMS or by Modbus TCP.
  • Operating hours counter for each manoeuvre output.
  • Configuration of the digital inputs to control the panel protections.
  • Time alarm to control the panel in a manual state or with the door open.
  • Three-phase electrical network analyzer with Active Energy and Reactive Energy Counters.
  • Recording of electrical parameters by phase with a programmable period.
  • Alarms for electrical parameters in full power or saving mode.
  • Record of the analogue input measurement in physical units.
  • Alarms of electrical parameters and programmable digital inputs for sending SMS.
  • Display and keyboard to verify the installation locally.

Technical specifications

  • 1 Astronomical Circuit (NC relay).
  • 1 Energy Saving Circuit (switched relay).
  • 2 Special Circuits (NC relay).
  • 10 A output relays (250 V a.c.) for a maximum load of 2.200 W.
  • 5 Digital Inputs for alarm control.
  • 1 Digital Input to control panel opening or additional alarm.
  • 1 Digital Input for manual selector control or for additional alarm.
  • 2 Digital Inputs can be used for pulse counting.
  • 3 Voltage Measurement Inputs per phase up to 300 V a.c. true effective value.
  • 3 Inputs for current measurement per phase up to 200 A a.c., by means of toroidal transformers (0-1.5 V a.c.).
  • 1 Analog Input 0-2 V a.c. for sensors (eg RMA25 for differential current measurement).
  • Exclusive long-life battery for the quartz watch.
  • LCD with intuitive symbols and texts.
  • 6 keys for programming and test function.
  • Leds to indicate the connection of each of the circuits.
  • 1 RS232 port for GPRS or Ethernet modem via Cnet-RS modem.
  • Operating temperature: -20ºC to +75ºC.
  • Power supply: 230 V a.c. ±15%, 50/60 Hz and own consumption of 7 VA.
  • 8-way DIN box for trans-panel mounting or symmetrical DIN rail.
  • Dimensions: 140 x 118 x 71 mm and weight of 700 gr.

Downloads

Datasheets and Brochure

  • TELEASTRO MB TCP ES
Request commercial information
c/ Provença, 533 Local A - 08025 Barcelona (Spain)
Tel. (+34) 934 463 050